| |
CHAPTER
44
FIRE HAZARD MITIGATION REQUIREMENTS
FOR NEW CONSTRUCTION
SECTION 4401 GENERAL
4401.1 Purpose. The purpose of this chapter is to establish minimum design
and construction standards for the protection of life and property from
fire, within the Urban Wildland Interface. These provisions are meant
to aid in the prevention and suppression of fires, and lessen the hazards
to structures from wildland fires as well as the hazards to wildlands
from structure fires.
4401.2 Scope. All new building construction, including any additions that
increase a building’s habitable floor area or number of stories,
shall comply with the provisions of this chapter.
EXCEPTION: Temporary buildings and buildings or structures used for the
sole purpose of providing shelter for agricultural implements, farm products,
livestock or poultry.
back to top
SECTION 4402 DEFINITIONS
For the purpose of this chapter, certain terms
are defined as follows:
ADEQUATELY MANNED STATION is a fire station having an average daily manning
of at least three fire fighters.
BUILDING SIZE as referenced in Section 4404 is the total floor area, as
defined in section R202, of all buildings located on the same property.
The area of an attached garage may be excluded from the total floor area
provided the garage is separated from the dwelling by a full one-hour
fire barrier. A building that is at least 50 feet away from another building
shall be considered separately in computing building size. Covered areas
that are at least 50% open on two or more sides shall not be included
in the computation of total floor area.
DEFENSIBLE SPACE is a designated area surrounding a building or buildings,
subject to approved fuel modification measures, intended to reduce fire-spread
potential between the structure and wildland.
Defensible Space shall extend to the distances specified in Table 44-A
(a minimum 30 feet for flat lots), or to the property lines, whichever
is less.
Defensible Space measurements shall commence from the building
plane, and follow all projections and recessions on each side of the building.
If a defensible space is required under these provisions for one building
or structure, then that mandatory defensible space shall also encompass
all appropriate buildings on the property located within a 50 foot radius
of the affected building. For any additions to an existing structure,
the defensible space shall be provided around the entire structure, including
the addition.
Within a defensible space, the following mitigation measures shall be
provided, subject to the exceptions contained herein:
- All slash and flammable debris shall be removed from all areas of a
defensible space, except as otherwise expressly designated by the inspector
(for example, small amounts may remain for habitat).
EXCEPTION: Firewood may be stored as follows: up to ten cubic feet – unregulated; stacks larger than ten cubic feet - minimum 10 foot distance
from the structure;
- All trees and shrubs located within 10 feet of the structure(s) shall
be removed.
EXCEPTION: A tree or shrub may remain within ten feet, provided the defensible
space distance is measured commencing from the tree’s drip edge
rather than from the building plane (so the tree is considered part of
or an extension of the structure), and provided the distance is not limited
by a property line.
- Trees and shrubs over 5 feet tall shall have an average crown spacing
of 10 feet from tree to tree. Groupings of trees may be allowed, provided
that all of the crowns in such group of trees are at least 10 feet from
the structure, and provided that the overall average tree spacing within
the defensible space is 10 feet (i.e. tree spacing around the grouping
is greater than 10’).
EXCEPTIONS:
(1) Aspens, narrowleaf cottonwoods, willows, and other trees
and shrubs listed in CSU Cooperative Extension publication 6.305 Firewise
Plant Materials, that are 10 or more feet from the structure may be spaced
closer than ten feet if expressly approved by the inspector.
(2) Closer
spacing of any trees may be allowed by the inspector upon a determination
that a 10-foot average spacing would put the remaining trees at undue
risk of wind-throw or snow breakage.
- Trees remaining within the defensible space shall have branches pruned
to a height of 10 feet, but notwithstanding said height requirement, branches
need not be pruned to more than 1/3 of the tree height.
EXCEPTIONS:
(1) Aspen trees.
(2). Isolated spruce and fir trees that are
at least 10 feet from the structure measured from the tree’s drip
edge.
back to top
FIRE-RESISTIVE CONSTRUCTION shall be defined as any one of the following:
Fire-resistive shell – exterior walls shall be a listed, one-hour
fire-resistive assembly, or log (6” min. dia.), and the roof shall
be protected by a layer of 5/8” type X gypsum board ceiling or nominal
2”x T&G wood ceiling. A non-combustible exterior wall surface
(cement stucco, brick, stone, cement fiber siding) may be used in lieu
of the exterior membrane of a listed wall assembly.Non-combustible construction – wall, floor, and roof framing, columns
and beams shall be of steel, concrete or masonry
MONITORED SMOKE ALARM SYSTEM shall be defined, permitted and inspected
through the responding fire district.
MUNICIPAL-TYPE WATER SUPPLY HYDRANT shall be defined as a water supply
hydrant that has the capacity to furnish, over and above domestic consumption,
a minimum flow of 1000 gpm and 20 psi residual pressure for a two-hour
duration.
RESPONSE ZONE represents the routine driving time from an adequately manned
station under optimal driving conditions, as determined by the fire department,
as follows: Zone 1-2: 5 minutes or less; Zone 3-4: more than 5 minutes
TREE CROWN is the needle or leaf bearing part of a tree. The crown edge
is the tree’s drip edge.
back to top
SECTION 4403 HAZARD RATINGS
Wildfire hazard rating. The Colorado State Forest Service shall assign
each subdivision, or portion thereof, a Wildfire Hazard Rating of “low”,
“moderate” or “high”. The rating will determine
the mitigation required for the construction.
The rating is based on criteria such as topography and type and extent
of vegetation. However, any subdivision located within response zone 1-2,
that is served by approved municipal water supply hydrants, and that is
served by year-round maintained roads which have an all weather surface
at least 22’ wide, will automatically receive a rating of low. For
any subdivision to receive consideration for an automatic low hazard rating,
all hydrants on such property must be municipal type water supply hydrants
as defined, must be located throughout the subdivision or portion thereof
and the hydrant spacing must be an average of not more than 500 feet.
back to top
SECTION 4404 REQUIRED MITIGATION
Class A Roof. All new construction, including additions, regardless of
the designated response zone or the wildfire hazard rating assigned to
the property, shall be provided with a class A roof as defined in R902.
Low Hazard. Construction in an area with a “Low” Fire Hazard
Rating shall require no additional mitigation measures beyond the installation
of a Class A roof.
Moderate Hazard. Construction in an area with a “Moderate” Fire Hazard Rating shall provide a defensible space area in accordance
with the requirements of this chapter and Table 44-A. Additionally, based
upon the higher fire loading potential, structures 6000 square feet and
larger in building size shall be provided with an automatic sprinkler
system, and structures 4000 s.f. to 6000 s.f. in building size shall implement
a fire-resistive construction measure as defined herein.
High Hazard. Construction in an area with a “High” Fire Hazard
Rating shall provide a defensible space area in accordance with the requirements
of this chapter and Table 44-A. Additionally, structures 4000 square feet
and larger in building size shall be provided with an automatic sprinkler
system, and structures ranging from 2400 s.f. up to 4000 s.f. in building
size shall implement a fire-resistive construction measure as defined
herein.
Additions. An addition located in a high or moderate wildfire hazard rated
subdivision, added to any structure built before January 1, 2000, will
require that a defensible space be provided around the addition as well
as the existing structure, in accordance with the requirements of this
chapter and Table 44-A. If the building size of the addition itself would
require fire-resistive construction by this chapter, the addition shall
be of fire-resistive construction but not the existing structure. If the
building size of the addition itself would require a sprinkler system
under this chapter, the entire building, including the additions, the
existing structure and any other applicable structures must be equipped
with a sprinkler system. An addition to a building that was previously
required to be of fire resistive construction or was required to have
a sprinkler system or monitored smoke detector system installed, will
require the same level of protection.
Alternates and Exceptions to Section 4404.
1) Unless otherwise required by this code, an automatic sprinkler system
may be installed in lieu of required fire-resistive construction.
2) A monitored smoke alarm system may be provided in lieu of fire-resistive
construction.
3) Alternate materials and methods, such as installing a draft hydrant
in lieu of fire-resistive construction, may be considered by the Building
Department in accordance with section R104.11 in its discretion on a case
by case basis.
4) Structures located in subdivisions that implement a CSFS approved subdivision-wide
fuel-reduction plan or defensible space plan will not require individual
defensible spaces.
back to top
TABLE 44-A --MINIMUM DEFENSIBLE SPACE DISTANCES
The minimum defensible space distance shall be 30 feet on level terrain,
plus modification to recognize the increased rate of fire spread at sloped
sites. Minimum distances for Defensible Space shall be directly from this
table or to the lot line, whichever is less.
NOTE: This table is based on Colorado State Forest Service publication
CSFS #143-691, Wildfire Protection in the Wildland Urban Interface.
back to top
|